Technicians checking refrigeration condensers on a supermarket roof with solar panels
Retail10 November 2026·7 min read

Supermarkets and retail: where the electricity goes and how to reduce it

A supermarket sells cold and light. Both are costly and run all day, and refrigeration alone is about half of the electricity bill.

In this article
  1. Refrigeration is about half of the bill
  2. Understanding the heat load on a cabinet
  3. The plant: head pressure, speed control and defrost
  4. Lighting and the heat it adds
  5. Rooftop solar and the retail load
  6. Protecting the stock during outages
  7. A sensible order of work
  8. How AVEX GRID helps

Key points

  • Refrigeration uses roughly half of a typical supermarket's electricity, according to the ASHRAE refrigeration handbook and field studies.
  • Most of the heat load on open cabinets is warm, humid store air getting in, so doors, covers and humidity control matter.
  • LED lighting cuts lighting energy and also reduces the heat the cooling plant must remove.
  • Controls such as floating head pressure, variable-speed fans and defrost on demand save energy without changing the shop floor.
  • Trading hours and refrigeration loads coincide with the sun, which makes rooftop solar a natural fit for retail.

Food retail runs on narrow margins. After stock and staff, electricity is one of the biggest costs you can control. A supermarket is also a very uniform kind of building. The same mix of refrigeration, lighting and air conditioning appears from store to store. So what you learn in one store carries over to another. This article shows where the energy goes, why, and what an engineer can do about it.

Refrigeration is about half of the bill

The ASHRAE Handbook on refrigeration is the standard reference for the industry. ASHRAE is the American society of heating, refrigerating and air-conditioning engineers. The handbook says refrigeration uses roughly 50% of the electricity in a typical supermarket. Independent studies of average-sized stores without air conditioning reached a similar result. Industry writers often quote a range of 40 to 60%. The exact figure depends on the climate, how much fresh food the store sells and the age of the plant. So any plan to cut a supermarket's electricity bill must start with refrigeration. Lighting and air conditioning matter, but they come second.

Understanding the heat load on a cabinet

Refrigeration energy depends on two things. One is how much heat the system must remove. The other is how efficiently it removes that heat. The heat comes from several sources. Heat passing through the walls and base of the cabinet is small in a well-built unit. Heat from the lights and fans inside the cabinet is more important. In an open multi-deck cabinet, the biggest part is usually infiltration. This is the warm, humid air from the store that is drawn into the curtain of cold air at the front of the unit. Infiltration brings in both heat and moisture. The moisture freezes on the cooling coil as frost. The system then has to melt that frost with defrost cycles, which use even more energy.

Several measures follow from this. Fit doors on the cabinets, or lids on chest freezers, to stop the warm air at the source. Evidence on the saving varies. Published figures for door retrofits range widely, depending on the type of cabinet and the store. Campaigners and manufacturers report cuts of up to about 40% of cabinet energy. Field trials of night covers report smaller cuts, of about 8%. Shoppers gain too, because the cold air no longer spills into the aisles and the store feels more comfortable. Control the store humidity with the air conditioning, and you reduce frost and the energy spent on defrosting. Keep the air curtains clean and correctly aligned. Never load the cabinets above the load line. This keeps the barrier that holds warm air out.

Reported energy saving from keeping cold air in the cabinetPercent of refrigeration energy
Night covers on open cabinets
8.5%
Doors on open cabinets (campaigners, up to)
up to 40%

The two figures come from different sources and methods; an audit measures the real saving for a given store. Source: University of Illinois SEDAC; The Daily Telegraph, 29 July 2019

The plant: head pressure, speed control and defrost

In many stores, the cabinets are served by a central rack of compressors, with condensers on the roof. A compressor is the machine that squeezes the refrigerant gas, and it is the biggest power user in the system. A condenser is the part that throws the collected heat away to the outside air. How well the rack works depends on the temperature at which it throws that heat away. A fixed, high condensing pressure wastes energy in the cooler hours. With floating head pressure control, the condensing temperature falls as the outside air cools. The compressors then use less power for the same cooling. Variable-speed fans on the condensers and evaporators save more power. This is because fan power rises with the cube of the speed, so a small cut in speed gives a big cut in power. Defrost on demand starts a defrost only when sensors measure frost build-up, not by the clock. This avoids heating the cooling coil when it is not needed, and it spares the cabinet that extra load.

Maintenance protects all these savings. A dirty condenser, a low refrigerant charge or a failed fan can raise energy use by a large margin. The cabinets can still stay cold enough, so nobody notices the loss. A monitoring system that records compressor currents, discharge pressures and cabinet temperatures makes these faults visible.

Lighting and the heat it adds

Lighting is the second largest electrical load in most stores. LED fittings (light-emitting diodes) give the same light as fluorescent and metal-halide lamps for a fraction of the power, and they give off less heat. The air conditioning and refrigeration plant must remove the heat from lights. So every watt you save on lighting also cuts cooling energy. Controls add to the saving. You can switch lights by zone, dim them where daylight is available, and put them on timers for cleaning and stocking after hours. Then the whole store is not lit when only one aisle is in use.

Rooftop solar and the retail load

A supermarket trades for long hours that match the sun, and its refrigeration runs all day. A rooftop solar array sized to the daytime load can supply a large share of the energy on site. You do not need batteries. Each unit saved is worth the full retail tariff, with its rates per unit and its fixed charges. This makes the economics simple. Rented premises need some thought. A tenant is someone who rents space and pays for the power they use. If the tenant pays the bill but the landlord owns the roof, a lease or a power purchase agreement can share the benefit fairly. A power purchase agreement is a long contract in which a buyer agrees to buy the electricity a plant makes at an agreed price. Our guide to solar feasibility shows how to test the economics. The article on tenant billing covers the arrangements for shopping centres.

Protecting the stock during outages

The refrigeration plant is the load that must not stop. Size a supermarket generator for the starting current of the compressors, because motors draw much more current as they start. Fit an automatic changeover, so the generator takes over without anyone present. In larger stores, add a sequenced restart so the compressors do not all start together. Temperature monitoring with alarms to the manager gives early warning of a fault. A lost cabinet costs you the stock. It can also bring food-safety problems. So the money spent on reliability is easy to justify.

A sensible order of work

An audit of a supermarket usually recommends the same order. First, log the main incomer and the refrigeration board for two weeks. Then repair doors, seals, air curtains and condensers, and set the store humidity correctly. Next, tune the refrigeration controls. After that, replace the lighting and add controls. Finally, size rooftop solar to the load that remains. Each step lowers the load for the next one. So the last measure, solar, is sized correctly and not oversized for a load that no longer exists.

How AVEX GRID helps

  • Retail energy audit. An energy audit is a survey of where a site uses energy and where it can save. We log the store, rank the measures by payback, and set the order of work.
  • Solar design. We size the roof array to your trading hours and prepare the registration papers.
  • Backup design. We design the standby supply and the restart sequence to protect the cold chain through outages. The cold chain means keeping fresh product cold at every step from the farm to the buyer. If one step fails, the product spoils.

What AVEX GRID can take off your hands

AVEX GRID is an engineer-led energy consultancy in Zimbabwe. We do the technical work that turns an energy investment into a plant that is licensed, connected, financed and performing, whether you are a local operator or an investor overseas.

Feasibility and bankable studiesYield, load and hybrid models, and the technical file lenders and ZERA read.
Power-system engineering (ETAP)Load flow, short circuit, arc flash and protection studies for approvals and safe design.
Licence and PPA technical supportZERA licence documents, ZETDC connection studies, PPA technical schedules.
Owner's engineerDesign review, testing and commissioning on your side of the EPC table.
Tariff, audit and compliance workMaximum-demand and power-factor savings, readiness for energy-management rules.
Remote plus on the groundModelling for overseas teams, with an engineer in Zimbabwe for site, utility and regulator work.

We quote fixed prices after a free scoping call and reply the same working day.

Frequently asked questions

What pays back fastest in a supermarket?

Repairs to door seals, air curtains and condensers, humidity control and refrigeration controls. They cost little and cut the cooling load immediately.

Are doors on open cabinets worth fitting?

In most stores yes. They reduce the largest heat load, improve temperature stability and make the aisles more comfortable. The size of the saving depends on the cabinet and the store, and an audit measures it.

Is LED lighting worth replacing now?

Yes. The energy saved is large, and the lower heat output reduces the cooling load as well.

How do we avoid stock loss in an outage?

With a generator sized for the compressors, an automatic changeover, a sequenced restart and temperature alarms that give early warning.

Topics: supermarket energy saving Zimbabwerefrigeration energy efficiencydisplay cabinet doorsLED lighting retailretail rooftop solarshopping centre energyretail energy auditenergy consultant Zimbabwe

Sources and notes

General information to help you plan. The rules that apply to your site are confirmed by AVEX GRID against the current gazetted text, ZERA and ZETDC as part of the work. The sources used are listed below.

DJ

Devine Tafara Javangwe is the founder and lead consulting engineer at AVEX GRID. He holds an MSc in Electrical Power Engineering (Southern Federal University, 2025), is a Professional Member of the Zimbabwe Institution of Engineers and an IEEE member.

About the practice · Contact

Take the cost out of the cold and the light.

Send us a year of bills for your store. We find the biggest savings and show you the payback before you spend.

+263 78 488 9775 · Autherstone Street 21, Marondera, Zimbabwe · Remote across Southern Africa