Thermal imaging for electrical faults: what it finds and how to act on it

A loose connection or an overloaded cable gets hot before it fails. A thermal camera shows the heat while the plant is running, so repairs can be planned.

In this article
  1. How a survey works
  2. What it finds
  3. Reading the severity
  4. Limits of the method
  5. Why it pays
  6. Survey frequency
  7. What a good thermal survey records
  8. From finding to repair
  9. How AVEX GRID helps

Key points

  • Electrical faults often produce heat long before they cause an outage. A thermal survey finds them while the plant is still in service.
  • A good survey is done under load. A connection that is cool at light load can be hot at full load.
  • Findings are ranked by the temperature rise over a reference, the load at the time and the criticality of the equipment.
  • Typical findings are loose or oxidised connections, unbalanced phases, overloaded cables and failing breakers or fuses.
  • Surveys are repeated on a schedule, so that new problems are found early and repairs are proved by a second image.

Heat is the most common early sign of an electrical fault. A connection with extra resistance turns part of the current into heat. The effect grows with the square of the current. So a joint that is only slightly warm at light load may be dangerous at full load. Thermal imaging measures that heat without touching the equipment.

How a survey works

  1. Plan. List the equipment: switchboards, motor control centres, transformers, bus bars, disconnects, large motors and critical circuits.
  2. Choose the conditions. The plant should run at a typical load, ideally more than half of its normal maximum. Write down the load during the survey.
  3. Scan. Covers are removed where it is safe, or the camera looks through inspection windows. The camera records images of each part and its surroundings.
  4. Compare. The thermographer is a trained person who takes and reads thermal camera images. The thermographer compares like with like, such as the three phases of the same connection. The thermographer also notes how many degrees hotter the part is than a reference.
  5. Report. Each finding is recorded with a thermal image and a normal photo. The report gives the measured temperature rise, the load and a recommended action.

What it finds

FindingTypical cause
One hot connection among three phasesLoose or oxidised joint on that phase
Uniformly warm conductorOverloaded cable or undersized conductor
Hot fuse or breakerPoor contact, ageing or overload
Warm transformer connection or bushingLoose terminal or internal problem
Hot bearing or motor housingMechanical wear, misalignment or lubrication fault

Reading the severity

Severity depends on three things: how far the temperature is above a reference, the load at the time, and what a failure would cost you. A small rise on a non-critical circuit can wait for the next planned outage. A large rise on a main incomer or a critical process needs action soon.

The ISO 18434 series of standards describes how to judge severity. ISO is the International Organization for Standardization, which writes international standards. The series covers thermography, overloads or failing equipment. Many sites also set their own priority bands in the maintenance plan.

Repair, then prove itAfter the repair, take a second image under a similar load. It shows whether the problem is solved. Keep both images in the record. They show the value of the survey and satisfy insurers and auditors.
How far above normal a connection runs, and what it meansTemperature rise above similar components under similar load, degrees Celsius
1 to 3 °C: possible deficiency, watch
up to 3 °C
4 to 15 °C: probable deficiency, repair soon
up to 15 °C
Above 15 °C: major discrepancy, repair now
over 15 °C

Bars show the upper limit of each band. A common industry guide; limits depend on the standard and the load at the time. Source: NETA maintenance testing specifications

Limits of the method

  • It sees surface temperature. Equipment behind closed panels needs inspection windows or safe access with covers off.
  • Shiny surfaces reflect heat and can mislead. A trained thermographer allows for this.
  • It only shows faults that produce heat. Other faults need other tests, such as insulation testing or power-quality measurement.

Why it pays

Plannedrepairs during scheduled outages, instead of breakdowns
Saferfewer hot joints in live equipment
Evidenceimages for maintenance records, insurers and audits

Survey frequency

Many sites survey critical electrical equipment once or twice a year, and other equipment once a year. Some plants should survey more often. These are plants with heavy loads, vibration, dust or heat, and plants that have had failures before. The right frequency follows the risk, so agree it with your maintenance team.

What a good thermal survey records

A thermal image on its own proves little. The value of a survey lies in the conditions and the comparisons that go with each image.

  • Load at the time. A connection that is sound at light load can run hot at full load. A survey is most useful when the equipment carries a normal working load. Write down the load at the time of each image.
  • A comparison, not just a number. The temperature of one phase is compared with the other phases, or with an identical part carrying the same current. A rise above the comparison matters more than the temperature itself.
  • The camera settings. Emissivity and reflected temperature affect the reading, especially on shiny metal. A careful survey records the settings used, so another engineer can repeat it.
  • A normal photograph of the same part, so you can find the finding again months later.
  • A ranking of findings. Findings are normally placed in bands by temperature rise. The bands run from "monitor", through "repair at the next planned outage", to "repair as soon as it is safe". Agree the bands with the client before the survey.

From finding to repair

Most hot spots come from loose, dirty or corroded connections, and from unbalanced or overloaded circuits. The fix is usually simple. Clean and re-tighten the connection, replace a worn part, or rebalance the load. What matters is that the repair is done safely, recorded, and checked with a second image afterwards. A survey that ends with a list and no follow-up image leaves one question open: is the fault really gone?

How AVEX GRID helps

  • Thermal surveys of switchboards, motor control centres, transformers and critical circuits.
  • Ranked findings with images, loads and recommended actions.
  • Follow-up checks and links to protection and power-quality studies, so that the root cause is fixed.

What AVEX GRID can take off your hands

AVEX GRID is an engineer-led energy consultancy in Zimbabwe. We do the technical work that turns an energy investment into a plant that is licensed, connected, financed and performing, whether you are a local operator or an investor overseas.

Feasibility and bankable studiesYield, load and hybrid models, and the technical file lenders and ZERA read.
Power-system engineering (ETAP)Load flow, short circuit, arc flash and protection studies for approvals and safe design.
Licence and PPA technical supportZERA licence documents, ZETDC connection studies, PPA technical schedules.
Owner's engineerDesign review, testing and commissioning on your side of the EPC table.
Tariff, audit and compliance workMaximum-demand and power-factor savings, readiness for energy-management rules.
Remote plus on the groundModelling for overseas teams, with an engineer in Zimbabwe for site, utility and regulator work.

We quote fixed prices after a free scoping call and reply the same working day.

Frequently asked questions

Does the plant need to shut down for a survey?

No. A survey is done while the plant is running under load. Some panels need covers removed, which is done with the site's safety procedures.

How long does a survey take?

It depends on the number of panels and their access. Most single-site surveys take a day or two.

Can thermal imaging find all electrical faults?

No. It finds faults that produce heat. It is one tool alongside insulation testing, protection testing and power-quality measurement.

What should I do with the findings?

Rank them by severity and criticality, plan repairs for the next suitable outage, and repeat the survey to confirm that each repair worked.

Topics: thermal imaging electrical inspectioninfrared survey switchboardthermography Zimbabwehot connection detectionpreventive maintenance electricalISO 18434electrical fire preventionenergy consultant Zimbabwe

Sources and notes

General information to help you plan. The rules that apply to your site are confirmed by AVEX GRID against the current gazetted text, ZERA and ZETDC as part of the work. The sources used are listed below.

DJ

Devine Tafara Javangwe is the founder and lead consulting engineer at AVEX GRID. He holds an MSc in Electrical Power Engineering (Southern Federal University, 2025), is a Professional Member of the Zimbabwe Institution of Engineers and an IEEE member.

About the practice · Contact

Find the hot connection before it finds you.

Tell us about your switchboards and motors. We propose a survey scope, the schedule and the report format that suits your maintenance plan.

+263 78 488 9775 · Autherstone Street 21, Marondera, Zimbabwe · Remote across Southern Africa